Georgetown University Enterprise Data Center HVAC System
Project Description
S.R. Gupta, P.C., as the Mechanical Engineer of Record, designed the HVAC system for the Georgetown University Enterprise Data Center in Laurel, Maryland, in 2008–2009. The system was engineered to support an initial rack density of 6.35 kVA/rack and 95.25 kVA/row, with scalability for future growth to 20 kVA/rack.
Technical Features
-
Cooling System
-
Deployed six Liebert DS 105 downflow units, with five units for normal operation and one for N+1 redundancy to ensure uninterrupted cooling during a unit failure.
-
Units were mounted on 18-inch pedestals to deliver cold air to cold aisles, with front-only access for simplified maintenance.
-
Implemented hot aisle containment with return vents placed in the hot aisles, directing exhaust air into a false ceiling plenum to prevent mixing with cold supply air, enhancing cooling efficiency.
-
Utilized a false ceiling plenum for return air management, simplifying design and supporting redundancy across the data center.
-
Selected R407A refrigerant to comply with the R22 phase-out (Montreal Protocol, Clean Air Act, post-2010), ensuring environmental compliance.
-
-
Thermal and Rack Density Management
-
Supported an initial rack density of 6.35 kVA/rack and 95.25 kVA/row, meeting 2008–2009 data center requirements.
-
Employed thermal dividers, to isolate hot and cold aisles, minimizing recirculation and preventing hotspots.
-
Designed for future scalability to 20 kVA/rack, with provisions for supplemental cooling (e.g., in-row coolers) to accommodate high-density loads like blade servers.
-
-
Reliability and Integration
-
Ensured N+1 redundancy through the ceiling plenum, enabling full cooling capacity during a single unit failure.
-
Configured controls to evenly distribute unit runtime, extending equipment lifespan and maintaining consistent performance.
-
Eliminated the raised floor to maximize rack space, integrating the ceiling plenum with lighting, fire suppression, and cabling to address spatial constraints.
-
Summary
The Georgetown University Enterprise Data Center HVAC system, delivered a robust and efficient cooling solution for a legacy data center. The innovative use of Liebert units on pedestals, hot aisle containment, and a false ceiling plenum supported an initial 6.35 kVA/rack and 95.25 kVA/row, with N+1 redundancy and scalability for future 20 kVA/rack loads. The R407A-based system ensured environmental compliance, while the design optimized space and reliability, meeting the data center’s mission-critical needs.