Engineering Silence and Precision for Cutting-Edge Medical Education
The W. Proctor Harvey Clinical Teaching Amphitheater at Georgetown University School of Medicine is a $10 million state-of-the-art facility dedicated to advancing clinical education. Named after Dr. W. Proctor Harvey, a pioneering cardiologist renowned for his auscultation expertise, the amphitheater hosts weekly grand rounds and immersive teaching sessions. Its advanced audiovisual (AV) systems, including a digital stethoscope broadcasting heart sounds to headphones with binaural sound capability, create an unparalleled learning environment.
The state of the art classroom features 308 seats and allows each of the students to plug in their laptop into the outlet directly on back of the seat in front of them while attending class, as well as the audio connection.
S.R. Gupta, P.C., as the MEP engineer of record, delivered an exceptionally quiet and responsive HVAC system. Partnering with SmithGroupJJR, a globally recognized leader in architecture and engineering, who served as the AOR, we worked seamlessly with with AV and lighting consultants to modernize the amphitheater in two phases.
The project was designed under the leadership of Dr. Ray Mitchell to meet the departments' requirements. The project was modeled in 3D using Revit during the schematic phase of design, with AutoCAD used for final construction drawings to communicate intricate details of construction.
The Challenge
The original classrooms (C104 and C105) in the Medical-Dental Building suffered from excessive mechanical noise from air handling units (AHU-1 and AHU-7) located directly below the seating, with return grilles transmitting disruptive noise into the teaching space. Sound frequencies of all ranges from low to high were noticeable in the space. The HVAC system faced high internal heat loads from AV equipment, lighting, and increased solar heat gain from the architect's desire to uncover the existing windows for more natural light into space. Ventilation for the 340-seat capacity and temperature control for transient high occupancy were also critical, alongside the need to serve adjacent lab spaces with the high air volume air handling unit.
Our Solution:
-
Redesigned the distribution ductwork, AHUs w/ VFDs and new return fans with VFDs, incorporated sound attenuators, and selected low-velocity diffusers to gain acoustic performance. Managed the return air path to prevent noise transmission, achieving a virtually silent HVAC system, ensuring flawless binaural audio playback without increased background sound levels. The Smithgroup was exceptional at designing the return air plenum employing mass loaded vinyl achieving STC 60 under the tiers, enabling the duct design to use offset elbows and other sound path termination methods to eliminate the return air fan noise from the space.
-
Advanced HVAC Design: Converted both units to a “hybrid-VAV” (Variable Air Volume) system with variable frequency drives (VFDs), providing precise airflow control to respond to rising internal heat gains from AV equipment, lighting, and solar loads without adversely affecting the required laboratory airflow. VFDs also offered future flexibility for lab and office spaces served by the same units. Equipped units with steam preheat coils and chilled water cooling coils for efficient thermal management, and hot water reheat in terminal units for precision temperature control and rapid response to high occupancy loads.
The system delivers large quantities of airflow without compromising acoustics.
Project Partners
-
Architect: SmithGroupJJR
-
AV Consultant: The Sextant Group
-
Lighting Consultant: MCLA
-
Construction: Patner Construction Inc.
Special thanks the American Testing and Balancing, Inc. for their excellent airflow measurement for this project both before and during commissioning. Implementation of the hybrid-vav system would have been difficult without their assistance and dedication.